Graco SMVector - Frequency Inverter Manuel d'utilisateur Page 46

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 66
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 45
45
SV01M
Commissioning
4.5.8 Onboard Communications Parameters 15-60HP (11-45kW)
The P6xx Onboard Communication parameters are applicable to the 15HP (11kW) and higher models only.
Code Possible Settings
IMPORTANT
No. Name Default Selection
p 0
Network Enable 0 Disabled This parameter enables the onboard network
communications.
1 Remote Keypad
2 Modbus
7 Lecom
NOTE: Onboard Communications will be
disabled if:
- P600 = 0, or
- P600 = 1 and P400 = 1, or
- P600 = 2 and P400 = 2, 3, 4, 5, 6 or 7
- P600 = 7 and P400 = 2, 3, 4, 5, 6 or 7
If the onboard communications are disabled,
the user will not have access to any of the other
P6xx parameters.
P 0
Network Address 1 - 247 Modbus
1 - 99 Lecom
P 1
Network Baud Rate 0 2400 bps 2 9600 bps Modbus
1 4800 bps 3 19200 bps
0 9600 bps Lecom
1 4800 bps
2 2400 bps
3 1200 bps
4 19200 bps
P 2
Network Data Format 0 8, N, 2 Modbus Only
1 8, N, 1
2 8, E, 1
3 8, O, 1
P 0
Network Control
Level
0 Monitor Only Lecom Only
1 Parameter Programming
2 Programming and Setpoint Control
3 Full Control
Network Powerup
Start Status
0 0 Quick Stop Lecom Only
1 Controller Inhibit
Network Timeout 0.0 - 300.0 seconds Modbus
0 - 65000 milliseconds Lecom
P
Network Timeout
Action
4 0 No action Modbus
1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.nF1
0 0 No action Lecom
1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1
P 7
Network Messages
Received
Read-Only: 0 - 9999 Valid network messages received
NOTE: When the number of messages exceeds 9999, the counter resets and resumes
counting from 0.
Vue de la page 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 65 66

Commentaires sur ces manuels

Pas de commentaire